 | Ratings: 2.5 to 500 HP at 230 VAC,
5 to 1100 HP at 460 VAC,
7.5 to 1400 HP at 575 VAC |
 | Soft start and stop |
 | Pulse/kick start |
 | Current limit |
 | 6 closed loop pump control curves |
 | Dual start/stop ramp adjustment |
 | Linear acceleration (user supplied tach) |
 | Two operating speeds (ratio speed of 1/6 rated speed) |
 | Adj slow speed torque control |
 | Final torque control: prevents excessive motor heating |
 | Electronic reversing at 1/6 speed |
 | Energy saving control: improves motor efficiency |
 | Opto-isolated control inputs |
 | SCR protection by metal oxide varistors |
 | Auxiliary contact: 1 SPOT, 8 amps, 250 VAC ('immediate') |
 | Auxiliary contact: 1 SPOT, 8 amps, 250 VAC ('end of acceleration') |
 | Alarm contact: 1 SPOT, 8 amps, 250 VAC |
 | Input from N.O. contact of External Fault |
 | Local / Remote reset (hard wired or through communication |
 | Motor FLA: min. of 50% of RVS-DN FLA |
 | 1 standard soft start/stop; 6 pump control curves |
 | Pulse start duration: 80% of voltage for 0.1-1 sec. |
 | Initial voltage: 10-50% of rated voltage |
 | Current limit: 100-400% of Motor FLA |
 | Acceleration time: 2-30 sec. |
 | Deceleration time: 2-30 sec. |
 | Electronic overload: Adjustable 75-150% of motor FLA |
 | Adj. time trip 9500% current 1-10 sec. |
 | Electronic fuse: during start-trips @ 850% current within 1 cycle; during run-trips
@ 200-850% within 1 cycle |
 | Undercurrent: 20-90% of current |
 | Undercurrent delay: 1-40 sec. |
 | Undervoltage: 120-600 V |
 | Undervoltage delay: 1-40 sec. |
 | Overvoltage: 150-750 V |
 | Overvoltage delay: 1 -10 sec. |
 | Max. start time: trips when ramp up exceeds 1-30 sec. |
 | Start inhibit: 1 -10 starts within 1-60 min |
 | Motor insulation: 0.2-5 Mohm alarm setting |
 | Dual adjustments:
Initial voltage: 10-50% of rated voltage
Current limit: 100-400% of Motor FLA
Accel and Decel time: 2-30 sec.
|