General Purpose AC Drive 3/4 - 500 HP
|
Performance Features:
 | Ratings: 0.75 to100HP at 208 VAC,
0.75 to100 HP at 230 VAC,
0.75 to 500 HP at 460 VAC,
2 to 200 HP at 600 VAC |
 | Overload capacity: 150% for 60 sec (200% peak) |
 | Starting torque: 150% |
 | Electronic reversing |
 | Adjustable accel/decel: 0.1 to 6000 sec |
 | Controlled speed range: (1) 40:1; (2) 100:1; (3) 1000:1 |
 | Drive efficiency: 96 to 98% |
 | Displacement power factor: 0.98 |
 | Output frequency: 0.1 to 400 Hz |
 | Jog forward and reverse |
 | Power loss ride-thru: 2 sec |
 | Inertia ride-thru |
 | Selectable auto restart after momentary power loss |
 | Programmable auto restart |
 | (0 to 10 attempts) on resettable fault |
 | Critical frequency rejection: |
 | 3 selectable, adjustable bands |
Protective Features:
 | DC bus CHARGE indicator |
 | Optically-Isolated controls |
 | Phase-to-phase / phase-to-neutral short circuit protection |
 | Ground fault protection |
 | Electronic motor overload (UL) |
 | Current and torque limit |
 | Overtorque/undertorque detection |
 | Fault circuit: overcurrent, overvoltage, and overtemperature |
 | Input/output phase loss |
Standards & Reliability:
 | UL and cUL listed |
 | IEC: 146A |
 | MTBF: Exceeds 28 years |
 | Circuit burn-in: 96 hours at 85 C |
 | Tested on fully-loaded motors |
 | Surface mount devices |
Service Conditions:
 | Ambient service temperature: |
 | -10 C to 40 C (104 F) Nema 1, to 45 C |
 | (113 F) protected chassis |
 | Humidity: non-condensing 95% |
 | Altitude: to 3300 feet |
 | Service factor: 1.0 |
 | Input voltage: +10%/-15%, 200 to 230 VAC, 380 to 460 VAC, 575 to 600 VAC |
 | Enclosure: NEMA 1 or protected chassis (other options) |
 | Input frequency: 50/60 Hz +/- 5% |
 | 3-phase, 3-wire, phase insensitive |
 | Vibration: 1G (to 20 Hz), 0.2G (20 to 50 Hz) |
Design Features:
 | 32-bit logic, including 16-bit DSP dependent on rating |
 | Alpha-numeric operator, removable, multi-lingual, 2 lines x 16 character 24 VDC control logic |
 | Programmable outputs one form A and two open collector |
 | Timer function |
 | RS-232 communication port |
 | Multi-speed settings: 9 available |
 | Remote speed reference: -10 to +10 VDC (20K ohms) or 4 to 20 mA (250 ohms) |
 | Setpoint (PID) control |
 | Signal follower: bias and gain |
 | Analog monitor output: -10 to +10 VDC proportional to output parameters |
 | DC bus reactor: 25 to 100 HP at 230 VAC, 30 to 250 HP at 460 VAC |
 | Dual motor parameter sets |
 | Auto-tune to motor characteristics |
 | Easy access, parameter groups |
 | Common bus capability |
 | Programmable flash ROM, via RS-232C, for custom applications Run and fault contacts (11A) |
 | Up / down / hold reference NEMA 1 enclosed or protected chassis |
Additional V/Hz Features:
 | DC injection braking: ramp or coast to stop, adjustable current limited to
60% motor rating |
 | Frequency resolution: 0.01 Hz w/ digital ref., 0.06 Hz w/ analog ref. |
 |
Frequency regulation: (15 to 35 C) 0.01 % w/ digital ref., 0.1 % w/ analog
ref. |
 |
Torque boost: full range, auto |
 |
Current limited stall prevention during accel, decel and run |
 |
Synchronized start into rotating motor via speed search |
 | Volts / hertz ratio: 15 preset and one infinitely-adjustable pattern |
 |
Slip compensation |
Additional Vector Control Features:
 |
Speed resolution: 0.01 % with digital reference, 0.1 % with analog reference |
 | Speed regulation: (15 to 35 C)
(2) 0.1 % with digital reference
(3) 0.01 % with digital reference
(3) 0.1 % analog reference |
 |
(3) Encoder response: 300 kHz
(3) Stall torque: to 150% at zero speed for 1 minute. 100% continuous |
Options:
 |
Remote operator stations |
 |
Pressure to electrical transducer |
 |
Input breaker, disconnect, fuses |
 |
Many control interface devices |
 |
NEMA 4 and 12 enclosures |
 |
RS-485 communication port |
 |
Isolation transformer |
 |
Analog monitor, precision |
 |
Digital or pulse monitor output |
 |
Additional form C contacts (2) |
 |
Synchronous motor operation |
 |
Dynamic braking |
 |
Dual PG card (digital follower) |
 |
Upload/download software |
 |
(1) 1000 Hz output |
 |
(3) Motor-mounted encoder |
 |
(3) PG card, A/B/Z phase line driver, +5 or +12 V supply |
 |
NEMA 1 options for protected chassis units.
|