GPD 506 with Bypass

GPD 506 Drive with Bypass Control

GPD 506 Features:

bullet Ratings:
0.75 to 100 HP at 208 VAC,
0.75 to 125 HP at 230 VAC,
0.75 to 500 HP at 460 VAC,
2.0 to 200 HP at 575 VAC, (consult factory)
bullet Overload capacity: 120% for 60 sec (180% peak)
bullet 150% starting torque capability, available from 1.5 Hz. to 60 Hz
bullet DC injection braking
bullet Electronic reversing
bullet Adjustable accel/decel: 0.1 to 3600 seconds (2 each)
bullet Controlled speed range of 40:1
bullet Critical frequency rejection: 2 adjustable bandwidths
bullet Torque limiting circuit: 30 to 180%
bulletGPD 506 efficiency: 96% at halt-speed; 98% at full-speed
bullet Energy $aving control: improves motor efficiency
bullet Displacement power factor: 0.98
bullet Output frequency: 0.1 to 400 Hz
bullet Frequency resolution:
0.01 Hz with digital reference,
0.06 Hz with analog reference
bullet Frequency regulation:
0.01 % digital (-10 to 40 C),
0.1 % analog (15 to 35 C)
bullet Torque boost: full range, auto
bullet Jog forward and reverse
bullet Power loss ride-thru: 2 sec
bullet Inertia ride-thru
bullet Selectable auto restart after momentary power loss
bullet Programmable auto restart (0 to 10 attempts) after resettable fault
bulletDC bus reactor: 25-100 HP at 208 VAC, 30-125 HP at 230 VAC, 30-250 HP at 460 VAC
bulletVolt, ammeter, kilowatt, elapsed run time meter functions
bullet Input and output terminal status indication
bullet Diagnostic fault indication
bullet S-curve (soft start/stop) capability
bullet Loss of input signal protection, with a speed default to a programmable percentage of the most recent speed
bullet"Up/Down" control capability
bullet Program security code
bullet 32 bit microprocessor based control circuit
bullet Programmable output contacts, one form C and one NO; selectable from 18 functions, including:
- Zero speed detection
- Low or high frequency detection
- Missing frequency reference
- Overtorque detection
bullet Five programmable input terminals; selectable from 27 functions, including:
-Remote/Local operation selection
-Detection of external overheat condition
-Preset speed selection
bullet Timer function: contact initiated
bullet Multi-speed settings: 6 available
bullet Signal follower: bias and gain
bullet The average MTBF (mean time between failure) is 28 years

 

Service Conditions:

bullet Ambient service temperature:
-10 C to 40 C (104 F)
bullet Ambient storage temperature:
-20 C to 60 C (140 F)
bullet 95% humidity: non-condensing
bullet Altitude: to 3300 ft, higher by derating
bullet Service factor: 1.0
bullet Vibration: 1 G. maximum under
20 Hz; 0.2 G at 20 Hz. to 60 Hz

 

C21 Style Bypass Features:

bullet Factory assembled; drive and bypass circuit electrically interlocked
bullet With motor in "bypass" mode, GPD 506 can be removed for service
bullet Enclosure: NEMA 1 or "NEMA 12 Type" filtered & blowered
bullet Remote speed reference: 0 to 10 VDC or 4 to 20 mA
bullet Setpoint (PID) control w/inverse input & sleep function
bullet Damper circuit safety interlock
bullet Running on drive, running on bypass and drive or motor fault contacts
bullet Optimized package for use with communication interfaces
bullet Easily accessible terminal strip for customer connections
bullet Analog monitor output: 0 to 10 VDC
bullet Circuit breaker disconnect, with interlocked, through-the-door operating mechanism
bullet Drive Input, Drive Output, and Bypass contactors
bullet Thermal overload relay, for motor protection in both "drive" and "bypass" modes
bullet 115 VAC control power transformer, fused
bullet "Drive Off / Bypass" selector switch
bullet "Auto Manual" selector switch
bullet "Normal / Test" selector switch
bullet "Power On" and "Fault" pilot lights

 

Operation:

bullet Output frequency and speed display, can be programmed for other speed-related indications, including RPM, CFM, FPM, and % max RPM
bullet Power loss ride-thru of 2 seconds
bulletInertia ride-thru
bullet GPD 506 accepts either a direct-acting or a reverse acting speed command signal
bullet "Speed Search" capability, to start a rotating load
bullet DC injection braking capability, to prevent fan "wind milling"
bullet Remote Run/Stop command input
bulletAn analog output of 0 to 10 VDC, proportional to output frequency, output current, or output power
bullet English language display, readout functions include: output frequency, output voltage, output current, output power, DC bus voltage, input terminal status, and fault status.
bullet Stall prevent (overload trip prevention)
bullet Over 100 programmable functions
bullet Either ramp-to-stop or coast-to-stop selection
bullet Auto restart: 0 to 10 attempts
bullet Volts/hertz ratio: One preset and 15 adjustable patterns
bullet Auto speed reference input signal, adjustable for bias and gain
bullet Programmable external fault input

While the GPID 506 is running, operational changes in control and display functions are possible:
bulletAccel/Decel time: 0 to 3600 seconds 
bulletFrequency reference command
bullet Forward / Reverse command
bullet Monitor display


Protective Features:

bullet Current limited stall prevention during accel, decel, and run conditions
bullet Synchronized start into rotating motor via speed search
bullet DC bus CHARGE indicator (inside GPD 506)
bullet Optically-isolated operator controls
bullet Phase-to-phase / phase-to-neutral short circuit protection
bullet Electronic ground fault protection
bullet Electronic thermal motor overload protection (UL approved)
bullet Current and torque limit
bullet Current limiting DC bus fuse
bullet Fault circuit: overcurrent, over-voltage, and overtemperature
bullet Heat sink over temperature protection
bullet Input / Output phase loss protection

 

Available Bypass Options:

bullet Input RFI Filter
bullet Input Fusing
bullet Input Reactor
bullet DC Bus Reactor (2 to 20 HP at 208 VAC, 2 to 25 HP at 230 VAC, 1 to 25 HP at 460 VAC)
bullet Pressure Transducer, 3-15 psi
bullet Smoke Purge Logic
bullet Auto Transfer on Drive Fault
bullet Other integrally mounted options for the GPD 506
bullet NEMA 4 or 3R enclosure (consult factory)

 

Building Automation Interface Options:

bullet System 600 Apogee FLN interface LonWorks interface
bullet Metasys N2 interface
bullet RS-485 interface option; RS-232 port for Mosbus RTU standard
bullet 4-20 mA output card



Quality Assurance:

In circuit testing of all printed circuit boards is conducted to insure proper mounting and correct value of all components

bullet Surface mount technology
bullet All printed circuit boards are burned in for 96 hours, at 85 C
bullet Final printed circuit board assemblies are functionally tested, via computerized test equipment
bullet All fully assembled controls are tested with fully loaded induction motors

 

Standards:

bullet UL listed
bullet cUL listed
bulletIEC: 146A

 

Y2K Compliant:

MagneTek drives have always been Year 2000 compliant and are able to correctly process dates within and between the 20th and 21st centuries.

 

GPD 506 Construction:

Input Section - GPD 506 power input stage converts three phase AC line power into a fixed DC voltage, via a solid state full wave diode rectifier, with MOV (Metal Oxide Varistor) protection. This design eliminates power line notching.

Intermediate Section - The DC bus maintains a fixed DC voltage, with filtering and short circuit protection and acts as a DC supply to the GPD 506 output section. It is interfaced with the GPD 506 diagnostic logic circuit, to continuously monitor and
protect the power components. A DC bus reactor is standard above 25 HP (optional below).

Output Section - Insulated Gate Bipolar Transistors (IGBT's) convert DC bus voltage to a variable frequency and voltage, utilizing a PWM sine-coded output to the motor. IGBT output, allowing motor noise, at 60 Hz, to measure less than 2 dB (@1 meter) above that resulting from across the line operation.

Non-Volatile memory (NV RAM); all programming memory is saved when the GPD 506 is disconnected from power.

Three current transformers, to detect the output current, for motor control and protective functions.

Digital operator keypad & display, provides local control, and readout functions:

bullet Run/Stop commands
bullet Speed Reference command
bullet Reset command
bullet English Language
bullet 2-Line 16 Character
 