Member of:

 

 

Official website of:

Federal Pump Corp.

                                                                                          Motors, Pumps, Controls, Drives, Hoists
HOME Up one level Feedback Request Quote SEARCH
GPD 333

General Purpose AC Drive 1/4 - 5 HP

 

NEMA 1

NEMA 4

                                   

Performance Features:

bullet Ratings: 1/4 to 5 HP at 230 VAC,
               1/4 to 5 HP at 460 VAC
bullet Constant torque overload rating: 150% for 1 min. (200% peak)
bullet DC injection braking, ramp to stop
bullet Electronic reversing
bullet Adjustable accel/decel: 0.1 to 600 seconds
bullet Controlled speed range: 40:1
bulletTorque limiting circuit: 30-200% of rated
bullet Drive efficiency: 95%
bullet Displacement power factor: 0.98
bullet Output frequency: 0.1 to 400 Hz
bullet Frequency resolution: 0.1 Hz with digital reference 0.06 /60 Hz with analog reference
bullet Frequency accuracy (-10 to 40 C): 0.01 % with digital command 0.1% with analog command
bullet Volts / hertz ratio: infinitely adjustable pattern
bulletDC injection braking: adjustable amplitude, duration, current limited
bullet Torque boost: full range, auto
bullet Power loss ride-thru: 1 sec
bullet Speed search
bulletAuto restart
bullet Critical frequency rejection

 

Design Features:

bullet 16-bit microprocessor logic
bulletLED status display
bullet Programmable form C contacts for customer use: 1A at 250 VAC or 30 VDC
bullet 24 VDC control logic
bullet Carrier frequency: 2.5-15 kHz
bullet Multi-speed settings: 5 (2-wire), 4 (3 wire)
bullet Remote speed reference: 0 -10 VDC (20K ohms) or 4 -20 mA (250 ohms)
bullet Signal follower: bias and gain
bullet Analog monitor output: 0-10 VDC proportional to output frequency or current
bullet Over 50 programmable functions
bulletNEMA 1 enclosed
bullet UL listed-, CSA approved; IEEE STD 444 (ANSi-C343); IEC: 146A
bullet Fully EMC compliant when optional FIR filter connected
bulletMTBF: exceeds 28 years



Protective Features:

bullet Current limited stall prevention during accel/decel and run
bullet DC bus CHARGE indicator
bullet Isolated operator controls
bulletPhase-to-phase / phase-to-neutral short circuit protection
bullet Ground fault protection UL 508C programmable electronic motor overload

 


Service Conditions:

bulletAmbient service temperature: -10 C to 45 C (14 to 113 F)
bulletAmbient storage temperature: -20 to 60 C (-4 to 140 F)
bulletHumidity: to 90% non-condensing
bulletAltitude: to 3300 ft; higher by derating
bulletService factor: 1.0
bulletInput voltage: +/- 10%
bullet 200 to 230 VAC, 380 to 460 VAC
bulletInput frequency: +/- 5% 50/6OHz
bullet3-phase, 3-wire, phase sequence insensitive


Options:

bulletDigital keypad operator
bulletRemote operator's station
bulletPressure to electrical transducer
bulletDynamic braking resistor
bulletInput circuit breaker / disconnect
bulletLine bypass with magnetic contactors
bulletMaster ratio module, voltage input
bulletPID controller module
bulletSet point controller module
bulletV / I converter module
bullet24 VDC control input card
bullet115 VAC control input card
bulletAnalog speed input card
bulletRemote interface panel (provides RS232 port)
bulletDin Rail Kit
bulletEnclosures: NEMA 1, 4 and 12
bulletSerial Communications choices

Top of Page