Type SP

SP Suggested Specs

Water Pressure Systems
Bulletin 271C

bullet

Automatic maintenance of building water pressure

bullet

Factory assembled and wired

bullet

Simplex, duplex, and triplex systems available

bullet

Cushion-Stop tanks available for low demand periods

SP systems are pre-assembled and pre-wired units which provide steady water pressure in buildings having varying water demand and variable street pressure.

The system includes close-coupled pumps, control valves, a temperature purge valve, copper suction and discharge headers, header pressure gauges, lag pump pressure control, pump isolation valves, a steel base, and a control panel (the panel comprises a fusible disconnect switch and magnetic starter for each pump motor, selector switches, pilot lights, a manual transfer switch, transformers, holding circuits and time delay relays).

Operation of the systems is as follows:

Simplex System: The pump operates continuously to satisfy the water demand.

Duplex System: The lead pump operates continuously to satisfy the water demand. When required, the lag pump is automatically started to run in parallel with the lead pump until the water demand drops again. The lag pump will then shut down. Lead and lag pumps are manually alternated.

Triplex Type A System: The first pump operates continuously to satisfy the water demand. When required, the second pump and then the third pump are automatically started to run in parallel with the first pump until the water demand drops again. The second and third pumps will then shut down. Pump sequence is manually alternated.

Triplex Type B System: A small capacity jockey pump operates continuously to satisfy the water demand. When required, the first main pump and then the second main pump are automatically started to run in parallel with the jockey pump until the water demand drops again. The main pumps will then shutdown. Sequence of the main pumps is manually alternated.

MODIFICATIONS AND ACCESSORIES
• 24-hour automatic alternation of lead pump.
• Alarm bell, silencer button and indicating light, plus cut-out circuit for high and low suction pressure and/or high and low system pressure.
• Flexible connectors for the ends of the headers and/or vibration rails for installation under the system base.
• Modified control panels and motor enclosures.
• Cushion-Stop tanks to shut down the lead pump during periods of low water demand.

SP CONTROL VALVES
Federal SP control valves perform the following functions:
(1) Automatically reduce a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate.
(2) Act as a check valve by preventing return flow when pressure reverses.
(3) Provide dampening action to eliminate pulsation caused by low flow rates.

The valves are of cast iron construction with bronze trim, and have an adjustable pressure range of 30-300 psig. 125# rated valves are standard but 250# rated valves are available if required. Maximum temperature rating is 180°F. The valve pressure setting is easily adjusted in the field with ordinary working tools.

SP PUMP AND MOTOR UNITS
Type SP water pressure systems are built with Federal Type CC, CG and CK close-coupled, bronze-fitted, end suction, centrifugal pumps. Pumps are back pull-out style with center-line discharge, and are fitted with leakless mechanical shaft seals. They are driven by standard JM type close-coupled pump motors.

SP CUSHION-STOP TANKS
SP systems can be furnished with a Cushion-Stop tank plus the circuitry required to shut off the lead pump. The tank is mounted on the same base as the pumps, and is furnished with all required piping, valves and controls. The tanks have a sealed inert flexible water chamber to separate the water and the air, and, therefore, no periodic recharging is necessary.

The standard Cushion-Stop tank has an 80 gallon nominal capacity and is rated for 150 psi maximum working pressure. Tanks with 125#, 175# and 250# ratings, tanks larger than the standard size and tanks with ASME labels are also available, if specified. The Cushion-Stop tank provides a cushion against leakage loss in the building and storage capacity for small water demand periods. They are, therefore, recommended for schools, office buildings, etc., with very low night-time and weekend water usage.

DETERMINING THE SP SYSTEM GPM RATING:
The total GPM rating of the SP system can be determined by using the fixture flow unit and conversion tables shown below.

Type Fixture

Public*

Semi Public*

Private*

Water Closet:

Flush valve

Flush tank

-

10

5

-

8

4

-

6

3

Urinal:

Flush valve, pedestal

Flush valve, stall or wall

Flush tank

-

10

5

3

-

8

4

2

-

-

3

-

Bath Tub

4

3

2

Shower

4

3

2

Lavatory (sink)

2

1

1

Bathroom Group (Water Closet plus Lavatory plus Tub Shower):

With flush valve

With flush tank

-

-

-

-

-

-

-

8

6

Sink:

Kitchen

General

Service

Lavatory

Bar

-

4

3

3

-

3

-

3

2

2

2

2

-

2

-

2

-

-

Dishwasher:

General

Pot and pan

Garbage Disposal, sink

Washing Machine

Laundry Tub

Drinking Fountain

Ice Cube Machine

Steamtables

Hose connection, 3/4"

Fire Sprinkler

-

6

3

3

-

-

2

1

1

-

10

-

4

3

3

6

3

1

1

1

4

10

-

2

-

2

4

3

1

1

-

4

-

*PUBLIC - Hospitals, hotels, factories, department stores, theatres, restaurants, schools, etc.
*SEMI-PUBLIC - Office buildings, clubs, motels, stores, etc.
*PRIVATE - Apartment buildings, homes, etc.

Note: Fixture Flow Unit Tables do not include air-conditioning, swimming pool, boiler make-up water requirements, etc. Actual GPM requirements for these demand factors should be added.

TOTAL FIXTURE FLOW UNITS

SYSTEM GPM

TOTAL FIXTURE FLOW UNITS

SYSTEM GPM

100

40

2000

210

200

70

2500

240

300

80

3000

270

400

90

3500

320

500

100

4000

350

750

115

5000

410

1000

120

6000

450

1250

150

7000

520

1500

170

8000

590

1750

190

9000

620

TO DETERMINE SP PUMP GPM RATING:
SIMPLEX SYSTEM: The pump should be rated for the full system GPM.
DUPLEX SYSTEM: Each of the two pumps should be rated for 70% of the system GPM.
TRIPLEX TYPE A SYSTEM: Each of the three pumps should be rated for 45% of the system GPM.
TRIPLEX TYPE B SYSTEM: Each of the two main pumps should be rated for 50% of the system GPM and the jockey pump should be rated for 25% of the system GPM.

TO DETERMINE PUMP HEAD:
(Total Dynamic Head Expressed in Feet)
(1) Vertical distance between pump and highest fixture.
(2) Plus friction loss through the piping system.
(3) Plus the pressure required at the highest fixture.
(4) Plus 10-ft. friction loss through the SP system.
(5) Less the minimum suction head available.
(PSI x 2.31 = Feet of Head.      Feet of head x .433 = PSI.)

Click Here for List Prices

Click Here for Suggested Specifications

SP Selection Table

System Number

GPM Each Pump*

Pump Head

Main Pump H.P.

Jockey Pump H.P. (Trip. B Only)

Conn. Size Simplex

Suction & Discharge Header Size

Main Control Valve Size

Jockey Valve Size (Trip. B) Only)

Lbs.

Feet

Duplex

Trip.A

 Trip.B

SP-4020-2

4030-2

4040-2

4050-2

4060-2

4070-2

4080-2

4090-2

40100-2

40

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

3

5

5

5

10

1

1

1

2

3

3

5

5

2

SP-6020-2

6030-2

6040-2

6050-2

6060-2

6070-2

6080-2

6090-2

60100-2

60

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

2

3

5

5

5

10

1

1

3

3

3

5

5

2

3

SP-8020-2

8030-2

8040-2

8050-2

8060-2

8070-2

8080-2

8090-2

80100-2

80

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

3

5

5

10

15

1

1

2

3

5

5

5

10

2

3

3

2

SP-10020-2

10030-2

10040-2

10050-2

10060-2

10070-2

10080-2

10090-2

100100-2

100

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

3

5

5

10

10

15

15

1

3

3

5

5

10

3

4

3

2

SP-12020-2

12030-2

12040-2

12050-2

12060-2

12070-2

12080-2

12090-2

120100-2

120

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

2

3

5

10

15

15

15

2

3

5

5

5

10

10

3

4

4

2

System Number

GPM Each Pump*

Pump Head

Main Pump H.P.

Jockey Pump H.P. (Trip. B Only)

Conn. Size Simplex

Suction & Discharge Header Size

Main Control Valve Size

Jockey Valve Size (Trip. B) Only)

Lbs.

Feet

Duplex

Trip.A

 Trip.B

SP-14020-2

14030-2

14040-2

14050-2

14060-2

14070-2

14080-2

14090-2

140100-2

140

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

3

5

10

10

15

15

20

2

3

5

10

10

4

4

4

SP-16020-2

16030-2

16040-2

16050-2

16060-2

16070-2

16080-2

16090-2

160100-2

160

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

3

5

10

10

15

15

20

20

3

5

5

10

15

3

4

5

4

SP-18020-2

18030-2

18040-2

18050-2

18060-2

18070-2

18080-2

18090-2

180100-2

180

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

5

5

10

10

15

15

20

20

3

5

5

10

10

15

3

4

5

4

SP-20020-2

20030-2

20040-2

20050-2

20060-2

20070-2

20080-2

20090-2

200100-2

200

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

5

10

15

15

15

20

25

3

5

5

10

10

15

15

3

4

5

5

3

SP-25020-2

25030-2

25040-2

25050-2

25060-2

25070-2

25080-2

25090-2

250100-2

250

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

5

10

15

15

15

20

25

25

2

3

5

10

10

15

15

3

5

6

5

3

2

SP-30020-2

30030-2

30040-2

30050-2

30060-2

30070-2

30080-2

30090-2

300100-2

300

20

30

40

50

60

70

80

90

100

45

70

95

115

140

160

185

210

230

15

15

20

20

25

30

30

3

5

10

15

15

20

20

4

5

6

5

3

2

DIMENSIONS

 

STANDARD DUPLEX SYSTEM

DUPLEX SYSTEM WITH CUSHION-STOP TANK

STANDARD TRIPLEX SYSTEM

TRIPLEX SYSTEM WITH CUSHION-STOP TANK

A

41

66

66

84

B

25

50

50

74

C

29

29

29

29

D

27

27

27

27

E

54

66

54

66

G

(4)

(4)

(4)

(4)

K

7/8

7/8

7/8

7/8

MOTOR FRAME

3450 RPM H.P.

1750 RPM H.P.

F

143JM

1-1/2

1

7-1/2

145JM

2-3

1½-2

7-1/2

182JM

5

3

8-1/2

184JM

7-1/2

5

8-1/2

213JM

10

7-1/2

9-1/4

215JM

15

10

9-1/4

254JM

20

15

10-1/4

256JM

25

20

10-1/4

284JM

30

25

11

TOTAL PUMP GPM

H

J

160 & less

2-1/2

2-1/2

161 thru 240

3

3

241 thru 420

4

4

421 thru 660

5

5

661 thru 900

6

6

 

Notes:
1.  Do not use dimensions for construction purposes unless certified.
2.  All dimensions are in inches unless otherwise noted.
3.  For dimensions of simplex systems, refer to ABC Electric Corp.
(4).  The 'G' dimension varies with the pump size, motor size and control valve size. Refer to ABC Electric Corp.
5.  Standard systems have suction coming in from the right and discharge going out to the right, facing the front of the system, as shown in the drawing above. The suction and/or discharge can be furnished on the left is so specified.