2" Discharge Sump Pumps
Bulletin
202B
 |
Vertical
Submerged |
 |
Heavy
Duty |
 |
Automatic |
 |
Single
or Duplex |
|
 |
For
Drainage |
 |
For
Seepage Water |
 |
For
Boiler Blow-Off |
 |
Pit
Covers |
|
 |
Grouting
Frames |
 |
Steel
Basins |
 |
Cast
Iron Basins |
|
 
FEATURES
MOTORS:
Nationally recognized manufacture in standard NEMA frame sizes and mounted on
rigid single piece cast iron pedestals, rabbetted to assure perfect alignment on
pump and motor shaft. Ball bearings are sealed against dirt and moisture and do
not require field lubrication. Motors on standard units are drip-proof. Totally
enclosed and explosion proof motors also available. Single phase (115/230v.)
motors have built-in thermal overload protection in fractional frame sizes.
Single phase motors in integral frame sizes and 3 phase (208 or 230/460 v.)
motors should be provided with magnetic starters.
FLOAT SWITCH:
Double break switch in steel enclosure, actuated by copper float, with brass rod
and stops.
FLEXIBLE COUPLING:
Precision machined with one-piece load cushion. No wear on metal jaws; load is
absorbed by cushion compression.
SUSPENSION PLATE:
Fourteen inch diameter cast iron suspension plate is standard. Twenty inch
diameter steel suspension plates also available.
HANGER PIPE:
Seamless steel pipe to insure rigid support for casing and accurate bearing
alignment.
DISCHARGE PIPE:
Discharge pipe firmly supported at floor plate to prevent piping strain on pump.
SHAFT:
Carbon steel, diameter sized to operate at maximum speed without vibration or
deflection. Micrometer adjustment provided above thrust bearing allows for
proper location of impeller and suction plate.
BEARINGS:
Oversize ball thrust bearing carries the weight of impeller and shaft; located
in a sealed housing fully protected from dirt and moisture. Bronze guide
bearings at pump casing and at intervals along shaft, prevent radial deflection.
Intermediate bearings are grease lubricated. Lower bearing is self-lubricating
and suitable for pumping hot or cold water. Special Teflon, Micarta, cutless
rubber and iron bearings, are also available if job conditions demand.
IMPELLER:
Single-piece cast bronze impeller, machined and balanced, held firmly against
shaft shoulder with key and lock nut.
CASING:
Centrifugal design, accurately machined for uniform clearance of impeller and
rigid connection to hanger pipe. Large area cast iron strainer fastened to
bottom of casing.
COVERS AND BASINS:
Pit covers are available for round, square, or rectangular sump pits. Covers can
be furnished with grouting frames if desired. Steel and cast iron sump basins of
all diameters and depths are also available. Covers and basins are fabricated to
suit pump suspension plates and control openings and include vent connection and
handhole or manhole. Basin inlet sizes and locations are determined by job
conditions.
MATERIALS OF CONSTRUCTION:
Standard bronze-fitted pumps have bronze impellers, pump bearing and
intermediate bearings. Casing, suction plate, motor pedestal and strainer are
cast iron suspension plate. Hanger pipe and discharge pipe are steel. Pumps of
all-bronze, all-iron, or stainless steel construction also available.
SINGLE AND DUPLEX UNITS:
Single units include one pump and motor, one float switch, one magnetic starter
(if required), and one pit cover or basin.
Duplex units include two pumps and motors, two float switches*, two magnetic
starters (if required), and one pit cover or basin.
*One alternating float switch can be furnished on duplex units, instead of
the two float switches, to alternate the operation of the two pumps, and to
provide two-pump simultaneous operation in the event one pump cannot handle the
in-flow.
Click Here for List Prices
Click Here for Parts List and
Prices
Click Here for Dimensions
Click Here for Performance Curves
| Selection Table |
| Unit No. |
GPM |
Disch. head (Ft.) |
Motor HP |
| 1750 RPM |
| VF-2 |
15
15
15 |
30
41
52 |
1/2
3/4
1 |
| VF-2 |
30
30
30
30 |
28
35
47
52 |
1/2
3/4
1
1-1/2 |
| VF-2 |
50
50
50
50 |
23
30
38
47 |
1/2
3/4
1
1-1/2 |
| VF-2 |
75
75
75
75 |
17
22
27
40 |
1/2
3/4
1
1-1/2 |
| VF-2 |
100
100
100
100 |
10
15
20
29 |
1/2
3/4
1
1-1/2 |
| VF-2 |
125
125
125 |
10
15
24 |
3/4
1
1-1/2 |
| 1150 RPM |
| VF-2 |
15
15
15
15 |
15
18
23
25 |
1/4
1/3
1/2
3/4 |
| VF-2 |
30
30
30
30 |
13
17
22
24 |
1/4
1/3
1/2
3/4 |
| VF-2 |
50
50
50
50 |
10
13
18
21 |
1/4
1/3
1/2
3/4 |
| VF-2 |
75
75
75 |
9
12
15 |
1/3
1/2
3/4 |

|
STANDARD ARRANGEMENTS FOR SUMP COVER PLATES AND PIT
FRAMES |
|
SIMPLEX COVERS

|
DUPLEX COVERS

|
| The above drawings of pit and basin cover
plates for Type VSP Sump Pumps show standard arrangements of Simplex and
Duplex Units for both circular and square plates. Square plates are
usually furnished for concrete pits, while circular plates are normally
furnished for cylindrical cast iron and steel basins. Fabricated steel
plates are furnished as standard. Steel plates of rectangular and
special shapes can be supplied, when specified. All cover plates are
treated with a corrosion resistant coating. |

Type PF-1 furnished as standard for square and rectangular pits. Permits
frame and cover to be installed flush with finished floor. Has bar support for
cover.
Type PF-2 construction same as PF-1 except with angle iron support for cover.
Type PF-3 furnished as standard for round pits. Frame supports cover and should
be recessed into concrete so that cover is flush with finished floor.
Type PF-4 construction same as PF-3 except with filler strip. Frames and covers
are treated with corrosion resistant coating, and are available in non-standard
shapes and sizes, sectional construction, and galvanized or checkered steel.

Pump Sizing Data
PUMP CAPACITY
Sump pump capacity can be selected from the following table, depending on the
type of soil in which the building foundation is located. The GPM ratings apply
to a single pump unit and to each pump of a duplex set.
| Sq. Ft. of Floor Space |
GPM (Clay Soil) |
GPM (Sandy Soil) |
| 0 to 2000 |
15 |
50 |
| 2000 to 4000 |
30 |
75 |
| 4000 to 6000 |
50 |
100 |
| 6000 to 10,000 |
75 |
125 |
| 10,000 to 15,000 |
100 |
150 |
| 15,000 to 20,000 |
125 |
200 |
| 20,000 to 30,000 |
150 |
250 |
| 30,000 to 40,000 |
200 |
300 |
If basement floor is more than 3 feet below sewer level, add 10% additional
pump capacity for each foot in excess of 3 feet. If building is located within
1000 feet of a river or lake, add 20% additional pump capacity.
PUMP DISCHARGE HEAD
The discharge head for a sump pump installation consists of the following
elements:
Static Head: The difference in elevation between the lowest water level in the
sump pit, and the maximum height of the discharge line.
Friction: Loss of head in the discharge line, including valves and other
fittings.
Back Pressure: Proper allowance must be made for back pressure in the sewer
line, if existing.
EXAMPLE
Sump pit 5' in depth to be set in ground, with top flush with finished floor.
Basement floor 10' below highest point of discharge line. Sump pump
capacity 50 GPM Size of discharge line 3".
Static Head --- 14 ft. *
Friction Head: discharge line -- 2 ft.
valves & other fittings --- 2 ft.
Back Pressure: --- 5 ft.
Total Dynamic Head: --- 23 ft.
* Lowest water level estimated to be 1ft. above bottom of sump pit.


Suggested Specifications for Architects and
Engineers
Furnish and install where shown on plans, Type VF-2 Simplex (or Duplex),
vertical, submerged, sump pump; as manufactured by the Federal Pump Corporation.
pump having a capacity of _____G.P.M. against a Total Dynamic Head of
_____feet. Pump to have 2" I.P.S. discharge and to be constructed for pit
(or basin) _____ft _____ins in depth. Shaft shall be carbon steel, and impeller
shall be bronze, open non-clog type. Ball thrust bearing shall be located in
dust and moisture-proof housing above suspension plate. Impeller to be
non-overloading at the H.P. specified throughout the entire range of operation.
Pumps to be driven through flexible coupling by _____H.P, _____R.P.M,
_____phase, _____cycles, _____volts, drip-proof motor.
(Each) Pump shall be controlled by an enclosed double-break float switch
actuated by copper float, brass rod and adjustable stops. (For duplex units,
specify: Furnish a pedestal mounted alternating float switch assembly with,
copper float, brass rod and adjustable stops, to alternate cycles of operation
of pumps and provide 2-pump operation under peak load condition).
Furnish built-in thermal overload protective device for single phase motors
in fractional H.P. frames. Furnish magnetic line voltage type starters for
single phase motors in integral H.P. frames and all 3 phase motors.
Steel pit cover to be furnished for concrete pit _____ft _____ins. by _____ft
_____ins., with necessary openings for pump, manhole, controls and vent
connection.
Welded angle iron grouting frame also to be furnished. If concrete pit is not
to be installed, specify: Furnish cast iron (or steel) basin _____ft _____ins,
in diameter and ft ins. in depth, complete with cover and inlets as required by
job conditions.
|