WIRING DIAGRAMS
SECTION 8
BULLETIN 257B

GENERAL NOTES
A.)   DISCONNECT SWITCHES OR CIRCUIT BREAKERS SHOULD BE INSTALLED IN POWER LINES AS REQUIRED BY APPLICABLE CODES.
B.)   MAGNETIC STARTERS CAN BE FURNISHED WITH "START-STOP" BUTTONS, "HAND-OFF-AUTOMATIC" SELECTOR SWITCHES, CONTROL CIRCUIT TRANSFORMERS, ISOLATED CONTROL CIRCUITS, PILOT LIGHTS, AND IN COMBINATION WITH FUSED OR UNFUSED DISCONNECT SWITCHES OR CIRCUIT BREAKERS.
C.)   MAGNETIC STARTERS HAVE OVERLOAD AND LOW VOLTAGE PROTECTION. STANDARD 3-PHASE STARTERS HAVE OVERLOAD RELAYS ON TWO PHASES. AN OVERLOAD RELAY FOR THE THIRD PHASE CAN BE INCLUDED.
D.)   MANUAL STARTERS PROVIDE OVERLOAD PROTECTION AND HAVE "ON-OFF" TOGGLE SWITCH. PILOT LIGHTS AND "HAND-OFF-AUTOMATIC" SWITCHES ARE ALSO AVAILABLE.
E.)   1-PHASE MOTORS IN FRACTIONAL HORSEPOWER FRAME SIZES ARE ORDINARILY CONSTRUCTED WITH BUILT-IN OVERLOAD PROTECTION AND THUS DO NOT REQUIRE MAGNETIC STARTERS UNLESS THEY ARE BEYOND THE ACROSS-THE-LINE CURRENT LIMITS OF THE PILOT CONTROL DEVICES. SEE WIRING DIAGRAMS FOR PILOT DEVICE CURRENT LIMITS.
F.)   SEE THE WIRING DIAGRAM INSIDE THE COVER OF MAGNETIC STARTERS FOR CORRECT CONTROL CIRCUIT COIL CONNECTIONS.
G.)   ALL WIRING SHOULD BE PROPERLY PHASED OUT.
H.)   REFER TO ABC ELECTRIC CORP FOR SPECIAL CONTROL SYSTEMS NOT ILLUSTRATED.

DIAGRAM #

DESCRIPTION

1- PHASE
WD101 Simplex Unit
Control switch starts & stops Pump.   (FS-1)
WD102 Duplex Unit
Control Switches start and stop their respective pumps.
The two control switches have different turn-on settings and thus provide 2-pump simultaneous operation only when required. (FS-2)
WD103 Simplex Unit
Manual Starter.
Control switch starts & stops Pump.   (FS-1)
WD104 Simplex Unit
Manual Starters.
Control switches start & stop their respective pumps.   (FS-2)
WD105 Simplex Unit
Magnetic Starter.
Control switch starts & stops Pump.   (FS-1)
WD106 Simplex Unit
Magnetic Starters.
Control switches start & stop their respective pumps.   (FS-2)
WD107A Duplex Unit
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.  (FS-3)
WD108A Duplex Unit
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required. Auxiliary float switch starts both pumps if alternating float switch is inoperative.  (FS-4)
WD109 Duplex Unit
Manual Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.  (FS-3)
WD110 Duplex Unit
Manual Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required. Auxiliary float switch starts both pumps if alternating float switch is inoperative.  (FS-4)
WD111 Duplex Unit
Magnetic Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.  (FS-3)
WD112 Duplex Unit
Magnetic Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required. Auxiliary float switch starts both pumps if alternating float switch is inoperative.  (FS-4)
WD113 Duplex Unit
Manual transfer selects lead pump and turns on lag pump for simultaneous operation when required. (5 amp max at 250V, 10 amp max at 125V)
WD114 Duplex Unit
Electric alternator starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.
WD115 Duplex Unit
Manual Starters
Manual transfer switch selects lead pump and turns on lag pump for simultaneous operation when required.
WD116 Duplex Unit
Manual Starters
Electric alternator starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.
WD117 Duplex Unit
Magnetic Starters
Manual transfer selects lead pump and turns on lag pump for simultaneous operation when required.
WD118 Duplex Unit
Magnetic Starters
Electric alternator starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.
WD119 Duplex Unit
Electric alternator starts and stops both pumps on an alternating basis
WD120 Duplex Unit
Manual transfer switch selects operating pump (5 amp max at 250V, 10 amp max at 125V)
WD121 High Water Alarm
Alarm sounds at predetermined high water level  (FS-5)
WD123 High Water Alarm
Alarm sounds at predetermined high water level. Bell is remote from actuator.  (FS-6)
WD124 High Water Alarm
Alarm sounds and indicating light goes on at predetermined high water level. Silencer button stops bell ring. Indicating light remains on until condition is corrected.
Bell  and Silencer are remote from actuator.
3- PHASE
WD301 Simplex Unit
Control switch starts & stops Pump.   (FS-1)
WD302 Duplex Unit
Control Switches start and stop their respective pumps.
The two control switches have different turn-on settings and thus provide 2-pump simultaneous operation only when required. (FS-2)
WD303 Simplex Unit
Magnetic Starter.
Control switch starts & stops Pump.   (FS-1)
WD304 Simplex Unit
Magnetic Starters.
Control switches start & stop their respective pumps.   (FS-2)
WD305 Duplex Unit
Manual Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.  (FS-3)
WD306 Duplex Unit
Magnetic Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.  (FS-3)
WD307 Duplex Unit
Magnetic Starters
Alternating Float switch starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required. Auxiliary float switch starts both pumps if alternating float switch is inoperative.  (FS-4)
WD308 Duplex Unit
Manual Starters
Manual transfer switch selects lead pump and turns on lag pump for simultaneous operation when required.
WD309 Duplex Unit
Magnetic Starters
Manual transfer selects lead pump and provides for simultaneous lag pump when required.
WD310 Duplex Unit
Magnetic Starters
Electric alternator starts & stops both pumps on an alternating basis and provides 2-pump simultaneous operation when required.
WD311 Duplex Unit
Magnetic Starters
Electric alternator starts and stops both pumps on an alternating basis
WD312 Duplex Unit
Magnetic Starters
Manual transfer switch selects operating pump
WD313 Triplex Unit
Magnetic Starters.
Manual transfer switch selects lead pump and provides 2-pump simultaneous operation when required, in the following sequences:
1-2-(3 standby); 2-3-(1 standby); 3-1-(2 standby).
WD314 Triplex Unit
Magnetic Starters.
Manual transfer switch selects lead pump and provides 2-pump and 3-pump simultaneous operation when required, in the following sequences:
1-2-3; 2-3-1; 3-1-2.