Member of:

 

 

Official website of:

Federal Pump Corp.

                                                                                          Motors, Pumps, Controls, Drives, Hoists
HOME Up one level Feedback Request Quote SEARCH
Type CCV

CCV Dimensions
CCV Suggested Specs
CCV Parts List

CONDENSATION RETURN UNITS
Bulletin 103E

bullet

Cast Iron or steel receivers

bullet1750 or 3450 RPM operation
bulletTo 100,000 sq. ft. E.D.R.
bulletTo 125 psig discharge pressure
bulletCompletely assembled
bulletControls mounted and wired

 

FEATURES

RECEIVER:
Cast iron receivers are standard. Steel receivers are available as an option. Maximum internal receiver pressure is 5 psi. Receivers are designed for venting  to atmosphere. 

PUMP: 
Bronze fitted centrifugal design, flanged to the receiver with leakless mechanical shaft seal. The seal chamber has a relief line back into the receiver to prevent air pockets or collection of abrasives near the mechanical seal. Motor and rotating assembly are removable without disturbing return or discharge piping. Maximum water temperature at pump suction is 210°F

MOTOR:
Drip-proof ball bearing design. Units are available with 1750 RPM or 3450 RPM motors. 

FLOAT SWITCH:
One for each pump, provides automatic operation, mounted and wired on unit. 

STARTERS: 
All polyphase units (200/230/460v), and integral HP, single phase units (115/230v) are furnished with magnetic starters mounted and wired on the unit. Single phase fractional HP motors have built-in overload protection and do not require magnetic starters.

 

MODIFICATIONS

Alternating Float Switch (Replaces the two standard float switches on a duplex unit, to automatically alternate cycle of operation, as well as providing 2-pump operation under peak conditions.)

Make-Up Water Valve (In lieu of float switches, where pumps are to be controlled by the boiler water level. The receiving tank size should be increased for make-up water storage)

* Combination Starters * Special Enclosures for Motors, Starters and Switches * Inlet Strainer for Receiver * Special Thermometers and Pressure Gauges * Galvanizing for Steel Receivers * Control Panels ( Wall, Floor or Unit Mounting) * Fractional HP Starters for Single Phase Units * Wall-Mounting Alternators * Non-Standard Receiver Sizes * Lead-Lag Pump Selection * Shut Off Valve for Pump Suction

 

Click Here for List Prices

Click Here for Parts Cross-Reference

Click Here for Dimensions

Click Here for Suggested Specs

 

Engineering Selection Table
Pump Disch Size & Type
Unit No.  Sq. Ft. EDR Pump Disch Press PSIG Pump Cap. GPM H.P. At 1750 RPM H.P. At 3450 RPM Rec. Cap. Gal. 1750 RPM 3450 RPM
CCV-210
CCV-215
CCV-220
CCV-230
CCV-240
CCV-250
CCV-260
CCV-270
CCV-280
2,000 10#
15
20
30
40
50
60
70
80
3 1/4
1/3
1/2
1
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
1-1/2
2
3
15 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-410
CCV-415
CCV-420
CCV-430
CCV-440
CCV-450
CCV-460
CCV-470
CCV-480
4,000 10#
15
20
30
40
50
60
70
80
6 1/4
1/3
1/2
1
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
1-1/2
2
3
15 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-610
CCV-615
CCV-620
CCV-630
CCV-640
CCV-650
CCV-660
CCV-670
CCV-680
6,000 10#
15
20
30
40
50
60
70
80
9 1/4
1/3
1/2
1
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
1-1/2
2
3
15 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-810
CCV-815
CCV-820
CCV-830
CCV-840
CCV-850
CCV-860
CCV-870
CCV-880
8,000 10#
15
20
30
40
50
60
70
80
12 1/4
1/3
1/2
1
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
1-1/2
2
3
15 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-1010
CCV-1015
CCV-1020
CCV-1030
CCV-1040
CCV-1050
CCV-1060
CCV-1070
CCV-1080
10,000 10#
15
20
30
40
50
60
70
80
15 1/4
1/3
1/2
1
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
1-1/2
2
3
15 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-1510
CCV-1515
CCV-1520
CCV-1530
CCV-1540
CCV-1550
CCV-1560
CCV-1570
CCV-1580
15,000 10#
15
20
30
40
50
60
70
80
22-1/2 1/4
1/3
1/2
1-1/2
2
3
5
7-1/2
-
1/3
1/3
1/3
1/2
3/4
1
2
3
3
25 1-1/4CCF
1-1/4CCF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-2010
CCV-2015
CCV-2020
CCV-2030
CCV-2040
CCV-2050
CCV-2060
CCV-2070
CCV-2080
20,000 10#
15
20
30
40
50
60
70
80
30 1/3
1/2
3/4
1-1/2
2
3
5
7-1/2
-
1/3
1/3
1/2
3/4
1
1-1/2
2
3
3
25 1CGF
1CGF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
CCV-2510
CCV-2515
CCV-2520
CCV-2530
CCV-2540
CCV-2550
CCV-2560
CCV-2570
CCV-2580
25,000 10#
15
20
30
40
50
60
70
80
37-1/2 1/3
1/2
3/4
1-1/2
2
3
5
7-1/2
-
1/3
1/3
1/2
3/4
1
2
3
5
5
35 1-1/2CGF
1-1/2CGF
1CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/2CGF
1CGF
1CGF
1CGF
CCV-3010
CCV-3015
CCV-3020
CCV-3030
CCV-3040
CCV-3050
CCV-3060
CCV-3070
CCV-3080
30,000 10#
15
20
30
40
50
60
70
80
45 1/3
3/4
1
1-1/2
2
3
5
7-1/2
-
1/3
1/2
1/2
3/4
1-1/2
2
3
5
5
35 1-1/2CGF
1CGF
1-1/2CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1CGF
1CGF
1CGF
1CGF
CCV-4010
CCV-4015
CCV-4020
CCV-4030
CCV-4040
CCV-4050
CCV-4060
CCV-4070
CCV-4080
40,000 10#
15
20
30
40
50
60
70
80
60 1/2
3/4
1
2
3
5
5
7-1/2
-
1/2
3/4
3/4
1
1-1/2
3
3
5
5
45 1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/2CGF
1CGF
1CGF
1CGF
CCV-5010
CCV-5015
CCV-5020
CCV-5030
CCV-5040
CCV-5050
CCV-5060
CCV-5070
CCV-5080
50,000 10#
15
20
30
40
50
60
70
80
75 3/4
1
1-1/2
2
3
5
7-1/2
7-1/2
-
3/4
3/4
1
1-1/2
2
3
5
5
5
70 1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/2CGF
1-1/2CGF
1-1/2CGF
1CGF
1CGF
CCV-6510
CCV-6515
CCV-6520
CCV-6530
CCV-6540
CCV-6550
CCV-6560
CCV-6570
CCV-6580
65,000 10#
15
20
30
40
50
60
70
80
97-1/2 3/4
1
1-1/2
3
3
5
7-1/2
10
-
1
1-1/2
1-1/2
2
3
5
7-1/2
7-1/2
10
70 1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CKF
1-1/2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CGF
CCV-7510
CCV-7515
CCV-7520
CCV-7530
CCV-7540
CCV-7550
CCV-7560
CCV-7570
CCV-7580
75,000 10#
15
20
30
40
50
60
70
80
112-1/2 3/4
1
1-1/2
3
5
7-1/2
10
15
-
1
1-1/2
2
3
5
5
7-1/2
10
10
70 1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CKF
2CKF
2CKHF
2CKHF
2CKHF
-
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/4CCF
1-1/2CGF
1-1/2CGF
1-1/2CGF
1-1/2CGF
CCV-10010
CCV-10015
CCV-10020
CCV-10030
CCV-10040
CCV-10050
CCV-10060
CCV-10070
CCV-10080
100,000 10#
15
20
30
40
50
60
70
80
150 1
1-1/2
2
3
5
7-1/2
10
15
-
1-1/2
2
3
5
7-1/2
7-1/2
10
10
10
120 2CGF
2CGF
2CGF
2CKF
2CKF
2CKHF
2CKHF
2CKHF
-
1-1/2CGF
1-1/2CGF
2CGF
2CGF
2CGF
2CGF
2CGF
1-1/2CGF
1-1/2CGF

Units operating at 1750 RPM, add -4 to unit number (example: CCV-1020-4); units operating at 3450 RPM, add-2 to unit number (example: CCV-1020-2). 
Units are available for discharge pressures higher than 80 PSIG, up to a maximum of 125 PSIG. Refer to an ABC Electric Corp. representative.