Bulletin 127D
Suggested Specifications for Architects and Engineers Furnish and install where indicated on plans, a Type BFC Simplex (or Duplex; Triplex; Quadruplex) Boiler Feed Unit, as manufactured by Federal Pump Corp., Unit No. BFC-_____ sized to provide feed water to _____boiler(s), (each) developing _____boiler H.P. (Each) pump shall deliver _____G.P.M. at a discharge pressure of _____PSIG at the pump(s). Unit shall be factory assembled by the pump manufacturer, including receiver and accessories plus pump(s) and motor(s) all mounted on a single steel base with pump suction piping complete. Pump(s) shall be close-coupled, end-suction, bronze-fitted, centrifugal type with balanced and enclosed impeller, leakless mechanical shaft seal and bronze shaft sleeve; driven by _____H. P., _____phase, _____cycles, _____volts, _____R.P.M. ball bearing, drip-proof (or totally enclosed; explosion-proof) motor(s). Single phase motors in fractional H.P. frame sizes shall have built-in thermal overload protection. Single phase motors in integral H.P. frame sizes and all three phase motors shall be provided with across-the-line type manual-reset magnetic starters in NEMA-1 general purpose (or NEMA-4 Water-tight; NEMA-7 Explosion-proof) wall-mounting enclosure(s). Receiver shall be of heavy steel construction, with anti-corrosion interior coating, gauge glass, thermometer, and connections for return, vent and drain. Makeup water valve, flange-mounted on tank head, shall be of all-bronze construction, float operated with makeup water strainer. Receiving tank capacity shall be _____gallons. Furnish and install on (each) boiler a boiler water level controller to automatically operate the pump(s), with low-water cut-off and alarm switch, plus alarm bell. Controller shall be equal to McDonnell-Miller No. 150 (for boiler pressures up to 150 P.S.I.) or No. 94 (for boiler pressures up to 250 P.S.I.). (Controllers not usually furnished by Federal).
FURNISH AND INSTALL AS SHOWN ON PLANS, A FEDERAL PUMP CORPORATION TYPE BFC DUPLEX BOILER FEED UNIT SIZED TO PROVIDE FEED WATER TO ONE BOILER. EACH PUMP SHALL BE SIZED AS SHOWN IN THE PUMP SCHEDULE.
THE UNIT SHALL BE FACTORY ASSEMBLED BY THE PUMP MANUFACTURER., INCLUDING THE FEED WATER RECEIVER, PUMP AND MOTOR UNITS, AND ACCESSORIES MOUNTED ON A STEEL BASE WITH PUMP SUCTION PIPING COMPLETE.
PUMPS SHALL BE CLOSE-COUPLED, END SUCTION, BRONZE-FITTED CENTRIFUGAL TYPE, WITH CENTERLINE DISCHARGE FOR AUTOMATIC VENTING. BACK PULLOUT DESIGN SHALL PERMIT REMOVAL OF THE MOTOR AND ROTATING ASSEMBLY WITHOUT DISTURBING PIPING. EACH PUMP SHALL HAVE AN ENCLOSED BALANCED BRONZE IMPELLER, MECHANICAL SHAFT SEAL AND COPPER BY-PASS FROM THE PUMP DISCHARGE INTO THE SEAL CHAMBER.
PUMPS SHALL BE CLOSE-COUPLED TO STANDARD NEMA JM-FRAME MOTORS IN OPEN, DRIP-PROOF ENCLOSURES, RATED. AS SHOWN IN THE PUMP SCHEDULE.
FURNISH A MAGNETIC STARTER FOR EACH MOTOR WITH OVERLOAD PROTECTION ON EACH PHASE AND A HAND-OFF-AUTOMATIC SELECTOR SWITCH. FURNISH A TRANSFER SWITCH TO PERMIT MANUAL SELECTION OF THE LEAD PUMP. STARTERS AND TRANSFER SWITCH SHALL BE FACTORY MOUNTED ON THE UNIT AND WIRED TO THE MOTORS. THE PUMPS SHALL BE CONTROLLED BY A BOILER WATER LEVEL CONTROLLER MOUNTED ON THE BOILER, AS HEREIN SPECIFIED.
THE FEED WATER RECEIVER SHALL BE OF HEAVY STEEL CONSTRUCTION WITH CONVEX HEADS, GAUGE GLASS, THERMOMETER, AND CONNECTIONS FOR RETURN, VENT, AND GRAIN. A MAKEUP WATER VALVE, FLANGE MOUNTED ON THE TANK HEAD, SHALL BE ALL-BRONZE, FLOAT OPERATED TYPE WITH STRAINER. THE RECEIVER CAPACITY SHALL BE AS SHOWN IN THE PUMP SCHEDULE.
PUMP SCHEDULE: No. of Boilers: __1__ No. of Pumps: __2__ Unit Model Number: __BFC-____________ Pumps: _____ GPM per Pump _____ PSI discharge Pressure Motors: _____ HP _____ RPM _____ Phase, 60 cycles, _____ volts Receiver: _____ Gallon Capacity Project: _________________________________ _________________________________
FURNISH AND INSTALL AS SHOWN ON PLANS, A FEDERAL PUMP CORPORATION TYPE BFC TRIPLEX BOILER FEED UNIT SIZED TO PROVIDE FEED WATER TO TWO BOILERS. EACH PUMP, SHALL BE SIZED AS SHOWN IN THE PUMP SCHEDULE.
THE UNIT SHALL BE FACTORY ASSEMBLED BY THE PUMP MANUFACTURER, INCLUDING THE FEED WATER RECEIVER, PUMP AND MOTOR UNITS, AND ACCESSORIES, MOUNTED ON A STEEL BASE WITH PUMP SUCTION PIPING COMPLETE.
PUMPS SHALL BE CLOSE-COUPLED, END SUCTION, BRONZE-FITTED CENTRIFUGAL TYPE, WITH CENTERLINE DISCHARGE FOR AUTOMATIC VENTING. BACK PULLOUT DESIGN SHALL PERMIT REMOVAL OF THE MOTOR AND ROTATING ASSEMBLY, WITHOUT DISTURBING PIPING. EACH PUMP SHALL HAVE AN ENCLOSED BALANCED BRONZE IMPELLER, MECHANICAL SHAFT SEAL AND COPPER BY-PASS FROM THE PUMP DISCHARGE INTO THE SEAL CHAMBER.
PUMPS SHALL BE CLOSE-COUPLED TO STANDARD NEMA JM-FRAME MOTORS IN OPEN, DRIP-PROOF, ENCLOSURES, RATED AS SHOWN IN THE PUMP SCHEDULE.
FURNISH A MAGNETIC STARTER FOR EACH MOTOR WITH OVERLOAD PROTECTION ON EACH PHASE AND A HAND-OFF-AUTOMATIC SELECTOR SWITCH. PUMP NO. 1 SHALL FEED BOILER No.1 AND PUMP No. 2 SHALL FEED BOILER No. 2. A MANUAL TRANSFER SWITCH SHALL PERMIT-PUMP NO. 3 TO ACT AS STANDBY FOR EITHER PUMP No.1 OR PUMP No. 2. STARTERS AND TRANSFER SWITCH SHALL BE FACTORY MOUNTED ON THE UNIT AND WIRED TO THE MOTORS. THE PUMPS SHALL BE CONTROLLED BY A BOILER LEVEL CONTROLLER MOUNTED ON EACH BOILER, AS HEREIN SPECIFIED.
THE. FEED WATER RECEIVER SHALL BE OF HEAVY STEEL CONSTRUCTION WITH CONVEX HEADS, GAUGE GLASS, THERMOMETER, AND CONNECTIONS FOR RETURN, VENT AND DRAIN. A MAKEUP WATER VALVE, FLANGE MOUNTED ON THE TANK HEAD, SHALL BE ALL-BRONZE, FLOAT OPERATED TYPE WITH STRAINER. THE RECEIVER CAPACITY SHALL BE AS SHOWN IN THE PUMP SCHEDULE.
PUMP SCHEDULE: No. of Boilers: __2__ No. of Pumps: __3__ Unit Model Number: __BFC-____________ Pumps: _____ GPM per Pump _____ PSI discharge Pressure Motors: _____ HP _____ RPM _____ Phase, 60 cycles, _____ volts Receiver: _____ Gallon Capacity Project: _________________________________ _________________________________ |