|
|
Suggested Specifications
Furnish and install as shown on plans, a factory-assembled duplex water pressure system equal to Federal Pump Corp. Model SP-____ The system shall include two close-coupled, bronze-fitted, end-suction centrifugal pumps, each rated ____GPM at ____ft. TDH. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor, ____HP, ____phase, ____cycle, ____volts, ____RPM. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch, required transformers, holding circuits and time delays, a lag pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, a pressure gauge for each header, an isolation valve on the the suction and discharge of each pump and a temperature sensing purge valve. The lead pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the lead pump to satisfy it, the system pressure will drop, causing the lag pump to start. Both pumps will operate in parallel for a set minimum time or until the demand in the building drops sufficiently to allow the lead pump to satisfy it alone, at which time the lag pump will shut down. The lead and lag pumps shall be manually alternated. CUSHION-STOP OPTION (add the following to the end of the specification):
Furnish and install as shown on plans, a factory-assembled triplex (Type B) water pressure system equal to Federal Pump Corp. Model SP-____ The system shall include three close-coupled, bronze-fitted, end-suction centrifugal pumps. The jockey pump shall be rated ____GPM at ____ft. TDH, and each of the main pumps shall be rated ____GPM at ____ft. TDH. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor, ____phase, ____cycle, ____volts, ____RPM. Jockey pump ____H.P. Main pumps ____H.P. each. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch, required transformers, holding circuits and time delays, a main pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, a pressure gauge for each header, an isolation valve on the the suction and discharge of each pump and a temperature sensing purge valve. The jockey pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the jockey pump to satisfy it, the system pressure will drop, causing the first main pump to start and operate in parallel with the jockey pump. After a set time delay period, the second main pump will start and operate in parallel with the other two pumps. After a set minimum time or when the demand in the building drops sufficiently to allow the jockey pump to satisfy it alone, the main pumps will shut down. The operating sequence of the main pumps shall be manually alternated. CUSHION-STOP OPTION (add the following to the end of the specification):
Suggested Specification Furnish and install as shown on plans, a factory-assembled duplex water pressure system equal to Federal Pump Corporation Type SP. The system shall include two close-coupled, bronze-fitted, end suction centrifugal pumps, each rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch, required transformers, holding circuits and time delays, a lag pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, and isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. The lead pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the lead pump to satisfy it, the system pressure will drop, causing the lag pump to start. Both pumps will operate in parallel for a set minimum time or until the demand in the building drops sufficiently to allow the lead pump to satisfy it alone, at which time the lag pump will shut down. The lead and lag pumps shall be manually alternated. OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE:
Suggested Specification Furnish and install as shown on plans, a factory-assembled duplex water pressure system equal to Federal Pump Corporation Type SP. The system shall include two close-coupled, bronze-fitted, end-suction centrifugal pumps, each rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch, required transformers, holding circuits and time delays, a lag pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, an isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. The lead pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the lead pump to satisfy it, the system pressure will drop, causing the lag pump to start. Both pumps will operate in parallel for a set minimum time or until the demand in the building drops sufficiently to allow the lead pump to satisfy it alone, at which time the lag pump will shut down. The lead and lag pumps shall be manually alternated. When the building water demand reaches a low level, the system pressure will rise, causing a pressure switch to shut off Pump #1. A Cushion-Stop tank will be integrally assembled on the system base. The tank shall be of the nominal capacity indicated in the pump schedule, and shall be rated for 150# maximum working pressure. The tank draw-down capacity will satisfy the small demand plus fixture leakage. When the demand increases, Pump #1 will start again, supplying the building demand, and returning the tank to full draw-down capacity for use on the next low demand cycle. OPTION: The Cushion-Stop tank shall carry an "ASME Code Construction" label showing a maximum working pressure rating of 125# (or 175# or 250#). OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE:
Suggested Specification Furnish and install as shown on plans, a factory-assembled triplex water pressure system equal to Federal Pump Corporation Type SP (Triplex B). The system shall include three close-coupled, bronze-fitted, end-suction centrifugal pumps. The jockey pump and the main pumps shall be rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch for the main pumps, required transformers, holding circuits and time delays, a main pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, an isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. The jockey pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the jockey pump to satisfy it, the system pressure will drop, causing the first main pump to start and operate in parallel with the jockey pump. After a set time delay period, the second main pump will start and operate in parallel with the other two pumps. After a set minimum time or when the demand in the building drops sufficiently to allow the jockey pump to satisfy it alone, the main pump will shut down. The operating sequence of the main pumps shall be manually alternated. OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE:
Suggested Specification Furnish and install as shown on plans, a factory-assembled triplex water pressure system equal to Federal Pump Corporation Type SP (Triplex B). The system shall include three close-coupled, bronze-fitted, end-suction centrifugal pumps. The jockey pump and the main pumps shall be rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a lead-lag manual transfer switch for the main pumps, required transformers, holding circuits and time delays, a main pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, an isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. The jockey pump shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of the jockey pump to satisfy it, the system pressure will drop, causing the first main pump to start and operate in parallel with the jockey pump. After a set time delay period, the second main pump will start and operate in parallel with the other two pumps. After a set minimum time or when the demand in the building drops sufficiently to allow the jockey pump to satisfy it alone, the main pumps will shut down. The operating sequence of the main pumps shall be manually alternated. When the building water demand reaches a low level, the system pressure will rise, causing a pressure switch to shut off Pump #1. A Cushion-Stop tank will be integrally assembled on the system base. The tank shall be of the nominal capacity indicated in the pump schedule, and shall be rated for 150# maximum working pressure. The tank draw-down capacity will satisfy the small demand plus fixture leakage. When the demand increases, Pump #1 will start again, supplying the building demand, and returning the tank to full draw-down capacity for use on the next low demand cycle. OPTION: The Cushion-Stop tank shall carry an "ASME Code Construction" label showing a maximum working pressure rating of 125# (or 175# or 250#). OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE:
Suggested Specification Furnish and install as shown on plans, a factory-assembled triplex water pressure system equal to Federal Pump Corporation Type SP (Triplex A). The system shall include three close-coupled, bronze-fitted, end-suction centrifugal pumps. The three pumps shall be of equal capacity and shall be rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with center-line discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a three-pump manual transfer switch, required transformers, holding circuits and time delays, a lag pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, an isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. Pump #1 shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of Pump #1 to satisfy it, the system pressure will drop, causing Pump #2 to start and operate in parallel with Pump #1. After a set time delay period, Pump #3 will start and operate in parallel with the other two pumps. After a set minimum time or when the demand in the building drops sufficiently to allow Pump #1 to satisfy it alone, Pump #2 and Pump #3 will shut down. The operating sequence of the three pumps shall be manually alternated. OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE:
Suggested Specification Furnish and install as shown on plans, a factory-assembled triplex water pressure system equal to Federal Pump Corporation Type SP (Triplex A). The system shall include three close-coupled, bronze-fitted, end-suction centrifugal pumps. The three pumps shall be of equal capacity and shall be rated as shown in the pump schedule. The pumps are to be of the back pull-out design, with centerline discharge, bronze shaft sleeve, enclosed bronze impeller and mechanical shaft seal. Each pump shall be driven by a drip-proof motor as detailed in the pump schedule. The system shall include a control valve for each pump which will act as a pressure reducing valve and a check valve. The system shall include a control panel in a NEMA-1 general purpose enclosure, factory mounted and wired on the unit, comprising a fusible disconnect switch for each motor with thru-door operating handles, a magnetic starter for each motor, HOA selector switches, pilot lights, a three-pump manual transfer switch, required transformers, hold-ing circuits and time delays, a lag pump control pressure switch and a terminal strip. The system shall be factory assembled on a steel base and shall include copper suction and discharge headers, brass/bronze interconnecting piping, a pressure gauge for each header, an isolation valve on the suction and discharge of each pump and a temperature sensing purge valve. Pump #1 shall operate continuously and its control valve shall maintain the system pressure. As water demand in the building increases beyond the ability of Pump #1 to satisfy it, the system pressure will drop, causing Pump #2 to start and operate in parallel with Pump #1. After a set time delay period, Pump #3 will start and operate in parallel with the other two pumps. After a set minimum time or when the demand in the building drops sufficiently to allow Pump #1 to satisfy it alone, Pump #2 and Pump #3 will shut down. The operating sequence of the three pumps shall be manually alternated. When the building water demand reaches a low level, the system pressure will rise, causing a pressure switch to shut off Pump #1. A Cushion-Stop tank will be integrally assembled on the system base. The tank shall be of the nominal capacity indicated in the pump schedule, and shall be rated for 150# maximum working pressure. The tank draw-down capacity will satisfy the small demand plus fixture leakage. When the demand increases, Pump #1 will start again, supplying the building demand, and returning the tank to full draw-down capacity for use on the next low demand cycle. OPTION: The Cushion-Stop tank shall carry an "ASME Code Construction" label showing a maximum working pressure rating of 125# (or 175# or 250#). OPTION: Furnish a low suction pressure cut-out switch with panel-front indicating light and required circuitry to stop pumps if suction pressure drops below a predetermined minimum level. (Note: Inclusion of this option is required by the N.Y.C. Plumbing Code.) PUMP SCHEDULE: |